Téléchargeur: Joshua
Pays: Japan
Temps de chargement: Jul 26, 2018
Prix: Gratuit
Évaluation: Basé sur 1 utilisateurs

S'il vous plaît, vérifiez que vous n'êtes pas un robot pour charger le reste des pages

tÉlÉcharger abb a95-30 contactor pdf

A95-30-11-80
A95-30-11 220-230V 50Hz / 230-240V 60Hz Contactor

General Information
Extended Product Type
A95-30-11-80
Product ID
1SFL431001R8011
EAN
7320500142776
Catalog Description
A95-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
Long Description
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and
Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50
and 60 Hz

Ordering
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Replacement Product ID (NEW)
1SBL407001R1311

Popular Downloads
Data Sheet, Technical Information
1SBC100122C0202
Instructions and Manuals
5309660-60
Dimension Diagram
53540923-1

Dimensions
Product Net Width
102.0 mm
Product Net Depth / Length
123.5 mm
Product Net Height
148.0 mm
Product Net Weight
2.040 kg

Technical
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50/60 Hz
Conventional Free-air Thermal Current (I th )
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 145 A
A95-30-11-80
2
Rated Operational Current AC-1 (I e )
(690 V) 55 °C 135 A
(690 V) 40 °C 145 A
(690 V) 70 °C 115 A
Rated Operational Current AC-3 (I e )
(1000 V) 55 °C 30 A
(415 V) 55 °C 96 A
(690 V) 55 °C 65 A
(220 / 230 / 240 V) 55 °C 96 A
(440 V) 55 °C 93 A
(380 / 400 V) 55 °C 96 A
(500 V) 55 °C 80 A
Rated Operational Power AC-3 (P e )
(500 V) 55 kW
(1000 V) 40 kW
(690 V) 55 kW
(220 / 230 / 240 V) 25 kW
(380 / 400 V) 45 kW
(440 V) 55 kW
(415 V) 55 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 160 A
Rated Short-time Withstand Current (I cw )
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
Maximum Electrical Switching Frequency
AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (I e )