Data sheet
6ES7134-4GD00-0AB0
SIMATIC DP, ELECTRONIC MODULE ET200S, 4AI STANDARD I2-WIRE, 4 - 20MA; 13BIT, 15MM WIDTH, FOR 2-WIRE
TRANSDUCER CYCLE TIME 40 MS/MODULE WITH LED SF
(GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC)
24 V; From power module
● Reverse polarity protection
Yes
Input current
from load voltage L+ (without load), max.
125 mA
from backplane bus 3.3 V DC, max.
10 mA
Output voltage
Power supply to the transmitters
● present
Yes
● short-circuit proof
Yes; approx. 200 mA for module
Power loss
Power loss, typ.
0.6 W
Address area
Address space per module
● Address space per module, max.
8 byte
Analog inputs
6ES7134-4GD00-0AB0
Page 1/3
18.02.2016
Changes preserved
© Copyright Siemens AG
Number of analog inputs
4
permissible input current for current input (destruction
limit), max.
30 mA; limited electronically
Cycle time (all channels) max.
40 ms; 33 to 40 ms
Input ranges
● Voltage
No
● Current
Yes
● Thermocouple
No
● Resistance thermometer
No
● Resistance
No
Input ranges (rated values), currents
● 4 mA to 20 mA
Yes; Into 25 Ohm
Cable length
● shielded, max.
200 m
Analog value generation for the inputs
Measurement principle
integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
13 bit; 4 to 20 mA: 13 bits
● Integration time, parameterizable
Yes
● Integration time (ms)
16,67 / 20 ms
● Interference voltage suppression for
interference frequency f1 in Hz
50 / 60 Hz
Smoothing of measured values
● parameterizable
Yes; in 4 stages
● Step: None
Yes; 1 x cycle time
● Step: low
Yes; 4 x cycle time
● Step: Medium
Yes; 16 x cycle time
● Step: High
Yes; 32 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max.
750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)
0.01 %
Temperature error (relative to input range), (+/-)
0.003 %/K
Crosstalk between the inputs, min.
-50 dB
Repeat accuracy in steady state at 25 °C (relative to
input area), (+/-)
0.05 %
Operational error limit in overall temperature range